Class: ASHRAE9012010

Inherits:
ASHRAE901 show all
Includes:
ASHRAE9012010CoolingTower
Defined in:
lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.rb,
lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.Model.rb,
lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.Space.rb,
lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.Model.rb,
lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.FanOnOff.rb,
lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.AirLoopHVAC.rb,
lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.ThermalZone.rb,
lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.Model.elevators.rb,
lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.FanVariableVolume.rb,
lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.FanConstantVolume.rb,
lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.FanVariableVolume.rb,
lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.CoolingTowerTwoSpeed.rb,
lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.CoolingTowerSingleSpeed.rb,
lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.CoolingTowerVariableSpeed.rb,
lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.AirTerminalSingleDuctVAVReheat.rb,
lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.AirTerminalSingleDuctVAVReheat.rb

Overview

This class holds methods that apply ASHRAE 90.1-2010 to a given model.

Constant Summary

Constants inherited from Standard

Standard::STANDARDS_LIST

Instance Attribute Summary collapse

Attributes inherited from Standard

#space_multiplier_map, #standards_data

Model collapse

Space collapse

FanOnOff collapse

AirLoopHVAC collapse

ThermalZone collapse

elevators collapse

FanVariableVolume collapse

FanConstantVolume collapse

AirTerminalSingleDuctVAVReheat collapse

Instance Method Summary collapse

Methods included from ASHRAE9012010CoolingTower

#cooling_tower_apply_minimum_power_per_flow_gpm_limit

Methods inherited from ASHRAE901

#fan_variable_volume_part_load_fan_power_limitation_capacity_limit

Methods inherited from Standard

#adjust_infiltration_to_lower_pressure, #adjust_infiltration_to_prototype_building_conditions, #adjust_sizing_system, #afue_to_thermal_eff, #air_loop_hvac_add_motorized_oa_damper, #air_loop_hvac_adjust_minimum_vav_damper_positions, #air_loop_hvac_adjust_minimum_vav_damper_positions_outpatient, #air_loop_hvac_allowable_system_brake_horsepower, #air_loop_hvac_apply_baseline_fan_pressure_rise, #air_loop_hvac_apply_economizer_integration, #air_loop_hvac_apply_economizer_limits, #air_loop_hvac_apply_energy_recovery_ventilator, #air_loop_hvac_apply_energy_recovery_ventilator_efficiency, #air_loop_hvac_apply_maximum_reheat_temperature, #air_loop_hvac_apply_minimum_vav_damper_positions, #air_loop_hvac_apply_prm_baseline_controls, #air_loop_hvac_apply_prm_baseline_economizer, #air_loop_hvac_apply_prm_baseline_fan_power, #air_loop_hvac_apply_prm_sizing_temperatures, #air_loop_hvac_apply_single_zone_controls, #air_loop_hvac_apply_standard_controls, #air_loop_hvac_apply_vav_damper_action, #air_loop_hvac_data_center_area_served, #air_loop_hvac_dcv_required_when_erv, #air_loop_hvac_demand_control_ventilation_required?, #air_loop_hvac_disable_multizone_vav_optimization, #air_loop_hvac_dx_cooling?, #air_loop_hvac_economizer?, #air_loop_hvac_economizer_required?, #air_loop_hvac_enable_demand_control_ventilation, #air_loop_hvac_enable_multizone_vav_optimization, #air_loop_hvac_enable_optimum_start, #air_loop_hvac_enable_supply_air_temperature_reset_delta, #air_loop_hvac_enable_supply_air_temperature_reset_outdoor_temperature, #air_loop_hvac_enable_supply_air_temperature_reset_warmest_zone, #air_loop_hvac_enable_unoccupied_fan_shutoff, #air_loop_hvac_energy_recovery?, #air_loop_hvac_energy_recovery_ventilator_heat_exchanger_type, #air_loop_hvac_energy_recovery_ventilator_required?, #air_loop_hvac_energy_recovery_ventilator_type, #air_loop_hvac_fan_power_limitation_pressure_drop_adjustment_brake_horsepower, #air_loop_hvac_find_design_supply_air_flow_rate, #air_loop_hvac_floor_area_served, #air_loop_hvac_floor_area_served_exterior_zones, #air_loop_hvac_floor_area_served_interior_zones, #air_loop_hvac_get_occupancy_schedule, #air_loop_hvac_humidifier_count, #air_loop_hvac_include_hydronic_cooling_coil?, #air_loop_hvac_include_wshp?, #air_loop_hvac_motorized_oa_damper_required?, #air_loop_hvac_multi_stage_dx_cooling?, #air_loop_hvac_multizone_vav_system?, #air_loop_hvac_optimum_start_required?, #air_loop_hvac_prm_baseline_economizer_required?, #air_loop_hvac_prm_economizer_type_and_limits, #air_loop_hvac_remove_motorized_oa_damper, #air_loop_hvac_residential_area_served, #air_loop_hvac_set_minimum_damper_position, #air_loop_hvac_static_pressure_reset_required?, #air_loop_hvac_supply_return_exhaust_relief_fans, #air_loop_hvac_system_fan_brake_horsepower, #air_loop_hvac_system_multiplier, #air_loop_hvac_terminal_reheat?, #air_loop_hvac_total_cooling_capacity, #air_loop_hvac_unitary_system?, #air_loop_hvac_unoccupied_fan_shutoff_required?, #air_loop_hvac_unoccupied_threshold, #air_loop_hvac_vav_damper_action, #air_loop_hvac_vav_system?, #air_terminal_single_duct_parallel_piu_reheat_apply_prm_baseline_fan_power, #air_terminal_single_duct_vav_reheat_apply_minimum_damper_position, #air_terminal_single_duct_vav_reheat_reheat_type, #air_terminal_single_duct_vav_reheat_set_heating_cap, #apply_changes_to_surface_construction, #apply_lighting_schedule, #apply_limit_to_subsurface_ratio, #apply_max_fdwr, #apply_max_srr, #boiler_hot_water_apply_efficiency_and_curves, #boiler_hot_water_find_capacity, #boiler_hot_water_find_search_criteria, #boiler_hot_water_standard_minimum_thermal_efficiency, build, #building_story_floor_multiplier, #building_story_minimum_z_value, #change_construction_properties_in_model, #chiller_electric_eir_apply_efficiency_and_curves, #chiller_electric_eir_find_capacity, #chiller_electric_eir_find_search_criteria, #chiller_electric_eir_standard_minimum_full_load_efficiency, #coil_cooling_dx_multi_speed_apply_efficiency_and_curves, #coil_cooling_dx_single_speed_apply_efficiency_and_curves, #coil_cooling_dx_single_speed_find_capacity, #coil_cooling_dx_single_speed_standard_minimum_cop, #coil_cooling_dx_two_speed_apply_efficiency_and_curves, #coil_cooling_dx_two_speed_find_capacity, #coil_cooling_dx_two_speed_standard_minimum_cop, #coil_cooling_water_to_air_heat_pump_apply_efficiency_and_curves, #coil_cooling_water_to_air_heat_pump_find_capacity, #coil_cooling_water_to_air_heat_pump_standard_minimum_cop, #coil_heating_dx_multi_speed_apply_efficiency_and_curves, #coil_heating_dx_single_speed_apply_defrost_eir_curve_limits, #coil_heating_dx_single_speed_apply_efficiency_and_curves, #coil_heating_dx_single_speed_find_capacity, #coil_heating_dx_single_speed_standard_minimum_cop, #coil_heating_gas_apply_efficiency_and_curves, #coil_heating_gas_apply_prototype_efficiency, #coil_heating_gas_multi_stage_apply_efficiency_and_curves, #coil_heating_water_to_air_heat_pump_apply_efficiency_and_curves, #coil_heating_water_to_air_heat_pump_find_capacity, #coil_heating_water_to_air_heat_pump_standard_minimum_cop, #combustion_eff_to_thermal_eff, #construction_calculated_solar_heat_gain_coefficient, #construction_calculated_u_factor, #construction_calculated_visible_transmittance, #construction_deep_copy, #construction_set_glazing_shgc, #construction_set_glazing_tvis, #construction_set_glazing_u_value, #construction_set_slab_f_factor, #construction_set_u_value, #construction_set_underground_wall_c_factor, #construction_simple_glazing?, #controller_water_coil_set_convergence_limits, #convert_curve_biquadratic, #cooling_tower_single_speed_apply_efficiency_and_curves, #cooling_tower_two_speed_apply_efficiency_and_curves, #cooling_tower_variable_speed_apply_efficiency_and_curves, #cop_heating_to_cop_heating_no_fan, #cop_to_eer, #cop_to_kw_per_ton, #cop_to_seer, #create_air_conditioner_variable_refrigerant_flow, #create_boiler_hot_water, #create_central_air_source_heat_pump, #create_coil_cooling_dx_single_speed, #create_coil_cooling_dx_two_speed, #create_coil_cooling_water, #create_coil_cooling_water_to_air_heat_pump_equation_fit, #create_coil_heating_dx_single_speed, #create_coil_heating_electric, #create_coil_heating_gas, #create_coil_heating_water, #create_coil_heating_water_to_air_heat_pump_equation_fit, #create_curve_bicubic, #create_curve_biquadratic, #create_curve_cubic, #create_curve_exponent, #create_curve_quadratic, #create_fan_constant_volume, #create_fan_constant_volume_from_json, #create_fan_on_off, #create_fan_on_off_from_json, #create_fan_variable_volume, #create_fan_variable_volume_from_json, #create_fan_zone_exhaust, #create_fan_zone_exhaust_from_json, #day_schedule_equivalent_full_load_hrs, #define_space_multiplier, #eer_to_cop, #fan_constant_volume_apply_prototype_fan_pressure_rise, #fan_on_off_apply_prototype_fan_pressure_rise, #fan_variable_volume_apply_prototype_fan_pressure_rise, #fan_variable_volume_cooling_system_type, #fan_variable_volume_part_load_fan_power_limitation?, #fan_variable_volume_part_load_fan_power_limitation_capacity_limit, #fan_variable_volume_set_control_type, #fan_zone_exhaust_apply_prototype_fan_pressure_rise, #film_coefficients_r_value, #find_and_set_insulation_layer, #find_exposed_conditioned_roof_surfaces, #find_exposed_conditioned_vertical_surfaces, #find_highest_roof_centre, #fluid_cooler_apply_minimum_power_per_flow, #get_outdoor_subsurface_ratio, #headered_pumps_variable_speed_set_control_type, #heat_exchanger_air_to_air_sensible_and_latent_apply_efficiency, #heat_exchanger_air_to_air_sensible_and_latent_apply_prototype_efficiency, #heat_exchanger_air_to_air_sensible_and_latent_apply_prototype_nominal_electric_power, #heat_exchanger_air_to_air_sensible_and_latent_minimum_efficiency, #heat_exchanger_air_to_air_sensible_and_latent_prototype_default_fan_efficiency, #heating_design_outdoor_temperatures, #hspf_to_cop_heating_no_fan, #hspf_to_cop_heating_with_fan, #intialize, #kw_per_ton_to_cop, #load_hvac_map, #load_initial_osm, #model_add_baseboard, #model_add_booster_swh_end_uses, #model_add_cav, #model_add_central_air_source_heat_pump, #model_add_chw_loop, #model_add_constant_schedule_ruleset, #model_add_construction, #model_add_construction_set, #model_add_crac, #model_add_crah, #model_add_curve, #model_add_cw_loop, #model_add_data_center_hvac, #model_add_data_center_load, #model_add_daylighting_controls, #model_add_design_days_and_weather_file, #model_add_district_ambient_loop, #model_add_doas, #model_add_doas_cold_supply, #model_add_elevator, #model_add_elevators, #model_add_evap_cooler, #model_add_exhaust_fan, #model_add_four_pipe_fan_coil, #model_add_furnace_central_ac, #model_add_ground_hx_loop, #model_add_ground_temperatures, #model_add_heatpump_water_heater, #model_add_high_temp_radiant, #model_add_hp_loop, #model_add_hvac, #model_add_hvac_system, #model_add_hw_loop, #model_add_ideal_air_loads, #model_add_low_temp_radiant, #model_add_material, #model_add_minisplit_hp, #model_add_piping_losses_to_swh_system, #model_add_prm_baseline_system, #model_add_psz_ac, #model_add_psz_vav, #model_add_ptac, #model_add_pthp, #model_add_pvav, #model_add_pvav_pfp_boxes, #model_add_radiant_proportional_controls, #model_add_refrigeration_case, #model_add_refrigeration_compressor, #model_add_refrigeration_system, #model_add_refrigeration_walkin, #model_add_schedule, #model_add_schedule_type_limits, #model_add_split_ac, #model_add_swh, #model_add_swh_booster, #model_add_swh_end_uses, #model_add_swh_end_uses_by_space, #model_add_swh_end_uses_by_spaceonly, #model_add_swh_loop, #model_add_typical_exterior_lights, #model_add_typical_refrigeration, #model_add_typical_swh, #model_add_unitheater, #model_add_vav_pfp_boxes, #model_add_vav_reheat, #model_add_vrf, #model_add_water_heater, #model_add_water_source_hp, #model_add_waterside_economizer, #model_add_window_ac, #model_add_zone_erv, #model_add_zone_ventilation, #model_apply_hvac_efficiency_standard, #model_apply_infiltration_standard, #model_apply_multizone_vav_outdoor_air_sizing, #model_apply_parametric_schedules, #model_apply_prm_baseline_skylight_to_roof_ratio, #model_apply_prm_baseline_window_to_wall_ratio, #model_apply_prm_construction_types, #model_apply_prm_sizing_parameters, #model_apply_standard_constructions, #model_assign_spaces_to_stories, #model_attach_water_fixtures_to_spaces?, #model_baseline_system_vav_fan_type, #model_create_exterior_lighting_area_length_count_hash, #model_create_prm_baseline_building, #model_create_space_type_hash, #model_create_story_hash, #model_cw_loop_cooling_tower_fan_type, #model_differentiate_primary_secondary_thermal_zones, #model_effective_num_stories, #model_elevator_fan_pwr, #model_elevator_lift_power, #model_eliminate_outlier_zones, #model_find_and_add_construction, #model_find_ashrae_hot_water_demand, #model_find_climate_zone_set, #model_find_constructions, #model_find_icc_iecc_2015_hot_water_demand, #model_find_icc_iecc_2015_internal_loads, #model_find_object, #model_find_objects, #model_find_prototype_floor_area, #model_find_target_eui, #model_find_target_eui_by_end_use, #model_find_water_heater_capacity_volume_and_parasitic, #model_get_baseline_system_type_by_zone, #model_get_building_climate_zone_and_building_type, #model_get_climate_zone_set_from_list, #model_get_construction_properties, #model_get_full_weather_file_path, #model_get_lookup_name, #model_get_or_add_ambient_water_loop, #model_get_or_add_chilled_water_loop, #model_get_or_add_ground_hx_loop, #model_get_or_add_heat_pump_loop, #model_get_or_add_hot_water_loop, #model_get_story_for_nominal_z_coordinate, #model_group_zones_by_story, #model_infer_hours_of_operation_building, #model_legacy_results_by_end_use_and_fuel_type, #model_make_name, #model_num_stories_spanned, #model_prm_baseline_system_change_fuel_type, #model_prm_baseline_system_group_minimum_area, #model_prm_baseline_system_groups, #model_prm_baseline_system_type, #model_prm_skylight_to_roof_ratio_limit, #model_process_results_for_datapoint, #model_remap_office, #model_remove_external_shading_devices, #model_remove_prm_ems_objects, #model_remove_prm_hvac, #model_remove_unused_resource_objects, #model_residential_and_nonresidential_floor_areas, #model_set_climate_zone, #model_setup_parametric_schedules, #model_standards_climate_zone, #model_system_outdoor_air_sizing_vrp_method, #model_typical_display_case_zone, #model_typical_hvac_system_type, #model_typical_walkin_zone, #model_validate_standards_spacetypes_in_model, #model_ventilation_method, #model_walkin_freezer_latent_case_credit_curve, #model_zones_with_occ_and_fuel_type, #planar_surface_apply_standard_construction, #plant_loop_apply_prm_baseline_chilled_water_pumping_type, #plant_loop_apply_prm_baseline_chilled_water_temperatures, #plant_loop_apply_prm_baseline_condenser_water_pumping_type, #plant_loop_apply_prm_baseline_condenser_water_temperatures, #plant_loop_apply_prm_baseline_hot_water_pumping_type, #plant_loop_apply_prm_baseline_hot_water_temperatures, #plant_loop_apply_prm_baseline_pump_power, #plant_loop_apply_prm_baseline_pumping_type, #plant_loop_apply_prm_baseline_temperatures, #plant_loop_apply_prm_number_of_boilers, #plant_loop_apply_prm_number_of_chillers, #plant_loop_apply_prm_number_of_cooling_towers, #plant_loop_apply_standard_controls, #plant_loop_capacity_W_by_maxflow_and_deltaT_forwater, #plant_loop_enable_supply_water_temperature_reset, #plant_loop_find_maximum_loop_flow_rate, #plant_loop_prm_baseline_condenser_water_temperatures, #plant_loop_supply_water_temperature_reset_required?, #plant_loop_swh_loop?, #plant_loop_swh_system_type, #plant_loop_total_cooling_capacity, #plant_loop_total_floor_area_served, #plant_loop_total_heating_capacity, #plant_loop_total_rated_w_per_gpm, #plant_loop_variable_flow_system?, #pump_variable_speed_set_control_type, register_standard, #remove_All_Subsurfaces, #remove_HVAC, #remove_air_loops, #remove_all_HVAC, #remove_all_plant_loops, #remove_all_zone_equipment, #remove_plant_loops, #remove_unused_curves, #remove_vrf, #remove_zone_equipment, #rename_air_loop_nodes, #rename_plant_loop_nodes, #safe_load_model, #safe_load_sql, #schedule_apply_parametric_inputs, #schedule_compact_annual_min_max_value, #schedule_constant_annual_equivalent_full_load_hrs, #schedule_constant_annual_min_max_value, #schedule_ruleset_annual_equivalent_full_load_hrs, #schedule_ruleset_annual_hourly_values, #schedule_ruleset_annual_hours_above_value, #schedule_ruleset_annual_min_max_value, #schedule_ruleset_cleanup_profiles, #schedule_ruleset_set_hours_of_operation, #seer_to_cop_cooling_no_fan, #seer_to_cop_cooling_with_fan, #set_VAV_terminals_to_control_for_outdoor_air, #set_Window_To_Wall_Ratio_set_name, #space_add_daylighting_controls, #space_apply_infiltration_rate, #space_conditioning_category, #space_cooled?, #space_daylighted_areas, #space_design_internal_load, #space_exterior_wall_and_roof_and_subsurface_area, #space_exterior_wall_and_window_area, #space_get_adjacent_space_with_most_shared_wall_area, #space_get_adjacent_spaces_with_shared_wall_areas, #space_heated?, #space_hours_of_operation, #space_plenum?, #space_residential?, #space_sidelighting_effective_aperture, #space_skylight_effective_aperture, #space_type_apply_internal_load_schedules, #space_type_apply_internal_loads, #space_type_apply_rendering_color, #space_type_get_construction_properties, #space_type_get_standards_data, #spaces_get_occupancy_schedule, #spaces_hours_of_operation, #standard_design_sizing_temperatures, #standards_lookup_table_first, #standards_lookup_table_many, #strip_model, #sub_surface_component_infiltration_rate, #sub_surface_create_centered_subsurface_from_scaled_surface, #sub_surface_create_scaled_subsurfaces_from_surface, #sub_surface_reduce_area_by_percent_by_raising_sill, #sub_surface_reduce_area_by_percent_by_shrinking_toward_centroid, #sub_surface_vertical_rectangle?, #surface_component_infiltration_rate, #surface_replace_existing_subsurfaces_with_centered_subsurface, #thermal_eff_to_afue, #thermal_eff_to_comb_eff, #thermal_zone_add_exhaust, #thermal_zone_add_exhaust_fan_dcv, #thermal_zone_add_unconditioned_thermostat, #thermal_zone_apply_prm_baseline_supply_temperatures, #thermal_zone_building_type, #thermal_zone_conditioning_category, #thermal_zone_convert_oa_req_to_per_area, #thermal_zone_cooled?, #thermal_zone_demand_control_ventilation_required?, #thermal_zone_design_internal_load, #thermal_zone_exhaust_fan_dcv_required?, #thermal_zone_floor_area_with_zone_multipliers, #thermal_zone_fossil_hybrid_or_purchased_heat?, #thermal_zone_fossil_or_electric_type, #thermal_zone_get_adjacent_zones_with_shared_wall_areas, #thermal_zone_get_occupancy_schedule, #thermal_zone_heated?, #thermal_zone_infer_system_type, #thermal_zone_majority_space_type, #thermal_zone_mixed_heating_fuel?, #thermal_zone_occupancy_type, #thermal_zone_outdoor_airflow_rate, #thermal_zone_outdoor_airflow_rate_per_area, #thermal_zone_plenum?, #thermal_zone_prm_baseline_cooling_design_supply_temperature, #thermal_zone_prm_baseline_heating_design_supply_temperature, #thermal_zone_residential?, #thermal_zone_vestibule?, #thermal_zones_get_occupancy_schedule, #true?, #validate_initial_model, #water_heater_mixed_apply_efficiency, #water_heater_mixed_apply_prm_baseline_fuel_type, #water_heater_mixed_find_capacity, #zone_hvac_component_apply_prm_baseline_fan_power, #zone_hvac_component_apply_standard_controls, #zone_hvac_component_apply_vestibule_heating_control, #zone_hvac_component_prm_baseline_fan_efficacy, #zone_hvac_component_vestibule_heating_control_required?

Methods included from PrototypeFan

apply_base_fan_variables, #create_fan_by_name, #get_fan_from_standards, #prototype_fan_apply_prototype_fan_efficiency

Methods included from CoilDX

#coil_dx_find_search_criteria, #coil_dx_heat_pump?, #coil_dx_heating_type, #coil_dx_subcategory

Methods included from CoolingTower

#cooling_tower_apply_minimum_power_per_flow, #cooling_tower_apply_minimum_power_per_flow_gpm_limit

Methods included from Pump

#pump_apply_prm_pressure_rise_and_motor_efficiency, #pump_apply_standard_minimum_motor_efficiency, #pump_brake_horsepower, #pump_motor_horsepower, #pump_pumppower, #pump_rated_w_per_gpm, #pump_standard_minimum_motor_efficiency_and_size

Methods included from Fan

#fan_adjust_pressure_rise_to_meet_fan_power, #fan_apply_standard_minimum_motor_efficiency, #fan_baseline_impeller_efficiency, #fan_brake_horsepower, #fan_change_impeller_efficiency, #fan_change_motor_efficiency, #fan_fanpower, #fan_motor_horsepower, #fan_rated_w_per_cfm, #fan_small_fan?, #fan_standard_minimum_motor_efficiency_and_size

Constructor Details

#initializeASHRAE9012010

Returns a new instance of ASHRAE9012010.



8
9
10
11
# File 'lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.rb', line 8

def initialize
  @template = '90.1-2010'
  load_standards_database
end

Instance Attribute Details

#templateObject (readonly)

Returns the value of attribute template.



6
7
8
# File 'lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.rb', line 6

def template
  @template
end

Instance Method Details

#air_loop_hvac_apply_multizone_vav_outdoor_air_sizing(air_loop_hvac) ⇒ Object

TODO:

move building-type-specific code to Prototype classes

Apply multizone vav outdoor air method and adjust multizone VAV damper positions to achieve a system minimum ventilation effectiveness of 0.6 per PNNL. Hard-size the resulting min OA into the sizing:system object.

return [Bool] returns true if successful, false if not



12
13
14
15
16
17
18
19
20
21
22
23
# File 'lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.AirLoopHVAC.rb', line 12

def air_loop_hvac_apply_multizone_vav_outdoor_air_sizing(air_loop_hvac)
  # First time adjustment:
  # Only applies to multi-zone vav systems
  # exclusion: for Outpatient: (1) both AHU1 and AHU2 in 'DOE Ref Pre-1980' and 'DOE Ref 1980-2004'
  # (2) AHU1 in 2004-2013
  # TODO refactor: move building-type-specific code to Prototype classes
  if air_loop_hvac_multizone_vav_system?(air_loop_hvac) && !(air_loop_hvac.name.to_s.include? 'Outpatient F1')
    air_loop_hvac_adjust_minimum_vav_damper_positions(air_loop_hvac)
  end

  return true
end

#air_loop_hvac_demand_control_ventilation_limits(air_loop_hvac) ⇒ Array<Double>

Determines the OA flow rates above which an economizer is required. Two separate rates, one for systems with an economizer and another for systems without. are zero for both types.

Returns:

  • (Array<Double>)
    min_oa_without_economizer_cfm, min_oa_with_economizer_cfm


275
276
277
278
279
# File 'lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.AirLoopHVAC.rb', line 275

def air_loop_hvac_demand_control_ventilation_limits(air_loop_hvac)
  min_oa_without_economizer_cfm = 3000
  min_oa_with_economizer_cfm = 1200
  return [min_oa_without_economizer_cfm, min_oa_with_economizer_cfm]
end

#air_loop_hvac_economizer_limits(air_loop_hvac, climate_zone) ⇒ Array<Double>

Determine the limits for the type of economizer present on the AirLoopHVAC, if any.

Returns:

  • (Array<Double>)
    drybulb_limit_f, enthalpy_limit_btu_per_lb, dewpoint_limit_f


28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
# File 'lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.AirLoopHVAC.rb', line 28

def air_loop_hvac_economizer_limits(air_loop_hvac, climate_zone)
  drybulb_limit_f = nil
  enthalpy_limit_btu_per_lb = nil
  dewpoint_limit_f = nil

  # Get the OA system and OA controller
  oa_sys = air_loop_hvac.airLoopHVACOutdoorAirSystem
  if oa_sys.is_initialized
    oa_sys = oa_sys.get
  else
    return [nil, nil, nil] # No OA system
  end
  oa_control = oa_sys.getControllerOutdoorAir
  economizer_type = oa_control.getEconomizerControlType

  case economizer_type
  when 'NoEconomizer'
    return [nil, nil, nil]
  when 'FixedDryBulb'
    case climate_zone
    when 'ASHRAE 169-2006-1B',
         'ASHRAE 169-2006-2B',
         'ASHRAE 169-2006-3B',
         'ASHRAE 169-2006-3C',
         'ASHRAE 169-2006-4B',
         'ASHRAE 169-2006-4C',
         'ASHRAE 169-2006-5B',
         'ASHRAE 169-2006-5C',
         'ASHRAE 169-2006-6B',
         'ASHRAE 169-2006-7A',
         'ASHRAE 169-2006-7B',
         'ASHRAE 169-2006-8A',
         'ASHRAE 169-2006-8B',
         'ASHRAE 169-2013-1B',
         'ASHRAE 169-2013-2B',
         'ASHRAE 169-2013-3B',
         'ASHRAE 169-2013-3C',
         'ASHRAE 169-2013-4B',
         'ASHRAE 169-2013-4C',
         'ASHRAE 169-2013-5B',
         'ASHRAE 169-2013-5C',
         'ASHRAE 169-2013-6B',
         'ASHRAE 169-2013-7A',
         'ASHRAE 169-2013-7B',
         'ASHRAE 169-2013-8A',
         'ASHRAE 169-2013-8B'
      drybulb_limit_f = 75
    when 'ASHRAE 169-2006-5A',
         'ASHRAE 169-2006-6A',
         'ASHRAE 169-2013-5A',
         'ASHRAE 169-2013-6A'
      drybulb_limit_f = 70
    end
  when 'FixedEnthalpy'
    enthalpy_limit_btu_per_lb = 28
  when 'FixedDewPointAndDryBulb'
    drybulb_limit_f = 75
    dewpoint_limit_f = 55
  end

  return [drybulb_limit_f, enthalpy_limit_btu_per_lb, dewpoint_limit_f]
end

#air_loop_hvac_economizer_type_allowable?(air_loop_hvac, climate_zone) ⇒ Bool

Check the economizer type currently specified in the ControllerOutdoorAir object on this air loop is acceptable per the standard.

Returns false if the economizer type is not allowable.

Returns:

  • (Bool)

    Returns true if allowable, if the system has no economizer or no OA system.



104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
# File 'lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.AirLoopHVAC.rb', line 104

def air_loop_hvac_economizer_type_allowable?(air_loop_hvac, climate_zone)
  # EnergyPlus economizer types
  # 'NoEconomizer'
  # 'FixedDryBulb'
  # 'FixedEnthalpy'
  # 'DifferentialDryBulb'
  # 'DifferentialEnthalpy'
  # 'FixedDewPointAndDryBulb'
  # 'ElectronicEnthalpy'
  # 'DifferentialDryBulbAndEnthalpy'

  # Get the OA system and OA controller
  oa_sys = air_loop_hvac.airLoopHVACOutdoorAirSystem
  if oa_sys.is_initialized
    oa_sys = oa_sys.get
  else
    return true # No OA system
  end
  oa_control = oa_sys.getControllerOutdoorAir
  economizer_type = oa_control.getEconomizerControlType

  # Return true if no economizer is present
  if economizer_type == 'NoEconomizer'
    return true
  end

  # Determine the prohibited types
  prohibited_types = []
  case climate_zone
  when 'ASHRAE 169-2006-1B',
       'ASHRAE 169-2006-2B',
       'ASHRAE 169-2006-3B',
       'ASHRAE 169-2006-3C',
       'ASHRAE 169-2006-4B',
       'ASHRAE 169-2006-4C',
       'ASHRAE 169-2006-5B',
       'ASHRAE 169-2006-6B',
       'ASHRAE 169-2006-7A',
       'ASHRAE 169-2006-7B',
       'ASHRAE 169-2006-8A',
       'ASHRAE 169-2006-8B',
       'ASHRAE 169-2013-1B',
       'ASHRAE 169-2013-2B',
       'ASHRAE 169-2013-3B',
       'ASHRAE 169-2013-3C',
       'ASHRAE 169-2013-4B',
       'ASHRAE 169-2013-4C',
       'ASHRAE 169-2013-5B',
       'ASHRAE 169-2013-6B',
       'ASHRAE 169-2013-7A',
       'ASHRAE 169-2013-7B',
       'ASHRAE 169-2013-8A',
       'ASHRAE 169-2013-8B'
    prohibited_types = ['FixedEnthalpy']
  when 'ASHRAE 169-2006-1A',
       'ASHRAE 169-2006-2A',
       'ASHRAE 169-2006-3A',
       'ASHRAE 169-2006-4A',
       'ASHRAE 169-2013-1A',
       'ASHRAE 169-2013-2A',
       'ASHRAE 169-2013-3A',
       'ASHRAE 169-2013-4A'
    prohibited_types = ['FixedDryBulb', 'DifferentialDryBulb']
  when 'ASHRAE 169-2006-5A',
       'ASHRAE 169-2006-6A',
       'ASHRAE 169-2013-5A',
       'ASHRAE 169-2013-6A'
    prohibited_types = []
  end

  # Check if the specified type is allowed
  economizer_type_allowed = true
  if prohibited_types.include?(economizer_type)
    economizer_type_allowed = false
  end

  return economizer_type_allowed
end

#air_loop_hvac_energy_recovery_ventilator_flow_limit(air_loop_hvac, climate_zone, pct_oa) ⇒ Double

Determine the airflow limits that govern whether or not an ERV is required. Based on climate zone and % OA. if nil, ERV is never required.

Returns:

  • (Double)

    the flow rate above which an ERV is required.



393
394
395
396
397
398
399
400
401
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417
418
419
420
421
422
423
424
425
426
427
428
429
430
431
432
433
434
435
436
437
438
439
440
441
442
443
444
445
446
447
448
449
450
451
452
453
454
455
456
457
458
459
460
461
462
463
464
465
466
467
468
469
470
471
472
473
474
475
476
477
478
479
480
481
482
483
484
485
486
487
488
489
490
491
492
493
494
495
496
497
498
499
500
501
502
503
504
505
506
507
508
509
510
511
512
# File 'lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.AirLoopHVAC.rb', line 393

def air_loop_hvac_energy_recovery_ventilator_flow_limit(air_loop_hvac, climate_zone, pct_oa)
  # Table 6.5.6.1
  case climate_zone
  when 'ASHRAE 169-2006-3B',
       'ASHRAE 169-2006-3C',
       'ASHRAE 169-2006-4B',
       'ASHRAE 169-2006-4C',
       'ASHRAE 169-2006-5B',
       'ASHRAE 169-2013-3B',
       'ASHRAE 169-2013-3C',
       'ASHRAE 169-2013-4B',
       'ASHRAE 169-2013-4C',
       'ASHRAE 169-2013-5B'
    if pct_oa < 0.3
      erv_cfm = nil
    elsif pct_oa >= 0.3 && pct_oa < 0.4
      erv_cfm = nil
    elsif pct_oa >= 0.4 && pct_oa < 0.5
      erv_cfm = nil
    elsif pct_oa >= 0.5 && pct_oa < 0.6
      erv_cfm = nil
    elsif pct_oa >= 0.6 && pct_oa < 0.7
      erv_cfm = nil
    elsif pct_oa >= 0.7 && pct_oa < 0.8
      erv_cfm = 5000
    elsif pct_oa >= 0.8
      erv_cfm = 5000
    end
  when 'ASHRAE 169-2006-1B',
       'ASHRAE 169-2006-2B',
       'ASHRAE 169-2006-5C',
       'ASHRAE 169-2013-1B',
       'ASHRAE 169-2013-2B',
       'ASHRAE 169-2013-5C'
    if pct_oa < 0.3
      erv_cfm = nil
    elsif pct_oa >= 0.3 && pct_oa < 0.4
      erv_cfm = nil
    elsif pct_oa >= 0.4 && pct_oa < 0.5
      erv_cfm = nil
    elsif pct_oa >= 0.5 && pct_oa < 0.6
      erv_cfm = 26_000
    elsif pct_oa >= 0.6 && pct_oa < 0.7
      erv_cfm = 12_000
    elsif pct_oa >= 0.7 && pct_oa < 0.8
      erv_cfm = 5000
    elsif pct_oa >= 0.8
      erv_cfm = 4000
    end
  when 'ASHRAE 169-2006-6B',
       'ASHRAE 169-2013-6B'
    if pct_oa < 0.3
      erv_cfm = nil
    elsif pct_oa >= 0.3 && pct_oa < 0.4
      erv_cfm = 11_000
    elsif pct_oa >= 0.4 && pct_oa < 0.5
      erv_cfm = 5500
    elsif pct_oa >= 0.5 && pct_oa < 0.6
      erv_cfm = 4500
    elsif pct_oa >= 0.6 && pct_oa < 0.7
      erv_cfm = 3500
    elsif pct_oa >= 0.7 && pct_oa < 0.8
      erv_cfm = 2500
    elsif pct_oa >= 0.8
      erv_cfm = 1500
    end
  when 'ASHRAE 169-2006-1A',
       'ASHRAE 169-2006-2A',
       'ASHRAE 169-2006-3A',
       'ASHRAE 169-2006-4A',
       'ASHRAE 169-2006-5A',
       'ASHRAE 169-2006-6A',
       'ASHRAE 169-2013-1A',
       'ASHRAE 169-2013-2A',
       'ASHRAE 169-2013-3A',
       'ASHRAE 169-2013-4A',
       'ASHRAE 169-2013-5A',
       'ASHRAE 169-2013-6A'
    if pct_oa < 0.3
      erv_cfm = nil
    elsif pct_oa >= 0.3 && pct_oa < 0.4
      erv_cfm = 5500
    elsif pct_oa >= 0.4 && pct_oa < 0.5
      erv_cfm = 4500
    elsif pct_oa >= 0.5 && pct_oa < 0.6
      erv_cfm = 3500
    elsif pct_oa >= 0.6 && pct_oa < 0.7
      erv_cfm = 2000
    elsif pct_oa >= 0.7 && pct_oa < 0.8
      erv_cfm = 1000
    elsif pct_oa >= 0.8
      erv_cfm = 0
    end
  when 'ASHRAE 169-2006-7A',
       'ASHRAE 169-2006-7B',
       'ASHRAE 169-2006-8A',
       'ASHRAE 169-2006-8B',
       'ASHRAE 169-2013-7A',
       'ASHRAE 169-2013-7B',
       'ASHRAE 169-2013-8A',
       'ASHRAE 169-2013-8B'
    if pct_oa < 0.3
      erv_cfm = nil
    elsif pct_oa >= 0.3 && pct_oa < 0.4
      erv_cfm = 2500
    elsif pct_oa >= 0.4 && pct_oa < 0.5
      erv_cfm = 1000
    elsif pct_oa >= 0.5 && pct_oa < 0.6
      erv_cfm = 0
    elsif pct_oa >= 0.6 && pct_oa < 0.7
      erv_cfm = 0
    elsif pct_oa >= 0.7 && pct_oa < 0.8
      erv_cfm = 0
    elsif pct_oa >= 0.8
      erv_cfm = 0
    end
  end

  return erv_cfm
end

#air_loop_hvac_integrated_economizer_required?(air_loop_hvac, climate_zone) ⇒ Boolean

Determine if the system economizer must be integrated or not. All economizers must be integrated in 90.1-2010

Returns:

  • (Boolean)


93
94
95
96
# File 'lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.AirLoopHVAC.rb', line 93

def air_loop_hvac_integrated_economizer_required?(air_loop_hvac, climate_zone)
  integrated_economizer_required = true
  return integrated_economizer_required
end

#air_loop_hvac_motorized_oa_damper_limits(air_loop_hvac, climate_zone) ⇒ Array<Double>

Determine the air flow and number of story limits for whether motorized OA damper is required.

Returns:

  • (Array<Double>)
    minimum_oa_flow_cfm, maximum_stories


284
285
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
303
304
305
306
307
308
# File 'lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.AirLoopHVAC.rb', line 284

def air_loop_hvac_motorized_oa_damper_limits(air_loop_hvac, climate_zone)
  case climate_zone
  when 'ASHRAE 169-2006-1A',
       'ASHRAE 169-2006-1B',
       'ASHRAE 169-2006-2A',
       'ASHRAE 169-2006-2B',
       'ASHRAE 169-2006-3A',
       'ASHRAE 169-2006-3B',
       'ASHRAE 169-2006-3C',
       'ASHRAE 169-2013-1A',
       'ASHRAE 169-2013-1B',
       'ASHRAE 169-2013-2A',
       'ASHRAE 169-2013-2B',
       'ASHRAE 169-2013-3A',
       'ASHRAE 169-2013-3B',
       'ASHRAE 169-2013-3C'
    minimum_oa_flow_cfm = 0
    maximum_stories = 999 # Any number of stories
  else
    minimum_oa_flow_cfm = 0
    maximum_stories = 0
  end

  return [minimum_oa_flow_cfm, maximum_stories]
end

#air_loop_hvac_multizone_vav_optimization_required?(air_loop_hvac, climate_zone) ⇒ Bool

TODO:

Add exception logic for systems with AIA healthcare ventilation requirements dual duct systems

Determine if multizone vav optimization is required.

Returns:

  • (Bool)

    Returns true if required, false if not.



190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
# File 'lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.AirLoopHVAC.rb', line 190

def air_loop_hvac_multizone_vav_optimization_required?(air_loop_hvac, climate_zone)
  multizone_opt_required = false

  # Not required for systems with fan-powered terminals
  num_fan_powered_terminals = 0
  air_loop_hvac.demandComponents.each do |comp|
    if comp.to_AirTerminalSingleDuctParallelPIUReheat.is_initialized || comp.to_AirTerminalSingleDuctSeriesPIUReheat.is_initialized
      num_fan_powered_terminals += 1
    end
  end
  if num_fan_powered_terminals > 0
    OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.AirLoopHVAC', "For #{air_loop_hvac.name}, multizone vav optimization is not required because the system has #{num_fan_powered_terminals} fan-powered terminals.")
    return multizone_opt_required
  end

  # Not required for systems that require an ERV
  if air_loop_hvac_energy_recovery?(air_loop_hvac)
    OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.AirLoopHVAC', "For #{air_loop_hvac.name}: multizone vav optimization is not required because the system has Energy Recovery.")
    return multizone_opt_required
  end

  # Get the OA intake
  controller_oa = nil
  controller_mv = nil
  oa_system = nil
  if air_loop_hvac.airLoopHVACOutdoorAirSystem.is_initialized
    oa_system = air_loop_hvac.airLoopHVACOutdoorAirSystem.get
    controller_oa = oa_system.getControllerOutdoorAir
    controller_mv = controller_oa.controllerMechanicalVentilation
  else
    OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.AirLoopHVAC', "For #{air_loop_hvac.name}, multizone optimization is not applicable because system has no OA intake.")
    return multizone_opt_required
  end

  # Get the AHU design supply air flow rate
  dsn_flow_m3_per_s = nil
  if air_loop_hvac.designSupplyAirFlowRate.is_initialized
    dsn_flow_m3_per_s = air_loop_hvac.designSupplyAirFlowRate.get
  elsif air_loop_hvac.autosizedDesignSupplyAirFlowRate.is_initialized
    dsn_flow_m3_per_s = air_loop_hvac.autosizedDesignSupplyAirFlowRate.get
  else
    OpenStudio.logFree(OpenStudio::Warn, 'openstudio.standards.AirLoopHVAC', "For #{air_loop_hvac.name} design supply air flow rate is not available, cannot apply efficiency standard.")
    return multizone_opt_required
  end
  dsn_flow_cfm = OpenStudio.convert(dsn_flow_m3_per_s, 'm^3/s', 'cfm').get

  # Get the minimum OA flow rate
  min_oa_flow_m3_per_s = nil
  if controller_oa.minimumOutdoorAirFlowRate.is_initialized
    min_oa_flow_m3_per_s = controller_oa.minimumOutdoorAirFlowRate.get
  elsif controller_oa.autosizedMinimumOutdoorAirFlowRate.is_initialized
    min_oa_flow_m3_per_s = controller_oa.autosizedMinimumOutdoorAirFlowRate.get
  else
    OpenStudio.logFree(OpenStudio::Warn, 'openstudio.standards.AirLoopHVAC', "For #{controller_oa.name}: minimum OA flow rate is not available, cannot apply efficiency standard.")
    return multizone_opt_required
  end
  min_oa_flow_cfm = OpenStudio.convert(min_oa_flow_m3_per_s, 'm^3/s', 'cfm').get

  # Calculate the percent OA at design airflow
  pct_oa = min_oa_flow_m3_per_s / dsn_flow_m3_per_s

  # Not required for systems where
  # exhaust is more than 70% of the total OA intake.
  if pct_oa > 0.7
    OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.AirLoopHVAC', "For #{controller_oa.name}: multizone optimization is not applicable because system is more than 70% OA.")
    return multizone_opt_required
  end

  # TODO: Not required for dual-duct systems
  # if self.isDualDuct
  # OpenStudio::logFree(OpenStudio::Info, "openstudio.standards.AirLoopHVAC", "For #{controller_oa.name}: multizone optimization is not applicable because it is a dual duct system")
  # return multizone_opt_required
  # end

  # If here, multizone vav optimization is required
  multizone_opt_required = true

  return multizone_opt_required
end

#air_loop_hvac_single_zone_controls_num_stages(air_loop_hvac, climate_zone) ⇒ Integer

Determine the number of stages that should be used as controls for single zone DX systems. 90.1-2010 depends on the cooling capacity of the system.

Returns:

  • (Integer)

    the number of stages: 0, 1, 2



315
316
317
318
319
320
321
322
323
324
325
326
327
# File 'lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.AirLoopHVAC.rb', line 315

def air_loop_hvac_single_zone_controls_num_stages(air_loop_hvac, climate_zone)
  min_clg_cap_btu_per_hr = 65_000
  clg_cap_btu_per_hr = OpenStudio.convert(air_loop_hvac_total_cooling_capacity(air_loop_hvac), 'W', 'Btu/hr').get
  if clg_cap_btu_per_hr >= min_clg_cap_btu_per_hr
    num_stages = 2
    OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.AirLoopHVAC', "For #{air_loop_hvac.name}: two-stage control is required since cooling capacity of #{clg_cap_btu_per_hr.round} Btu/hr exceeds the minimum of #{min_clg_cap_btu_per_hr.round} Btu/hr .")
  else
    num_stages = 1
    OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.AirLoopHVAC', "For #{air_loop_hvac.name}: two-stage control is not required since cooling capacity of #{clg_cap_btu_per_hr.round} Btu/hr is less than the minimum of #{min_clg_cap_btu_per_hr.round} Btu/hr .")
  end

  return num_stages
end

#air_loop_hvac_supply_air_temperature_reset_required?(air_loop_hvac, climate_zone) ⇒ Bool

Determine if the system required supply air temperature (SAT) reset. For 90.1-2010, SAT reset requirements are based on climate zone.

Returns:

  • (Bool)

    Returns true if required, false if not.



334
335
336
337
338
339
340
341
342
343
344
345
346
347
348
349
350
351
352
353
354
355
356
357
358
359
360
361
362
363
364
365
366
367
368
369
370
371
372
373
374
375
376
377
378
379
380
381
382
383
384
385
386
387
# File 'lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.AirLoopHVAC.rb', line 334

def air_loop_hvac_supply_air_temperature_reset_required?(air_loop_hvac, climate_zone)
  is_sat_reset_required = false

  # Only required for multizone VAV systems
  unless air_loop_hvac_multizone_vav_system?(air_loop_hvac)
    return is_sat_reset_required
  end

  case climate_zone
  when 'ASHRAE 169-2006-1A',
       'ASHRAE 169-2006-2A',
       'ASHRAE 169-2006-3A',
       'ASHRAE 169-2013-1A',
       'ASHRAE 169-2013-2A',
       'ASHRAE 169-2013-3A'
    OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.AirLoopHVAC', "For #{air_loop_hvac.name}: Supply air temperature reset is not required per 6.5.3.4 Exception 1, the system is located in climate zone #{climate_zone}.")
    return is_sat_reset_required
  when 'ASHRAE 169-2006-1B',
       'ASHRAE 169-2006-2B',
       'ASHRAE 169-2006-3B',
       'ASHRAE 169-2006-3C',
       'ASHRAE 169-2006-4A',
       'ASHRAE 169-2006-4B',
       'ASHRAE 169-2006-4C',
       'ASHRAE 169-2006-5A',
       'ASHRAE 169-2006-5B',
       'ASHRAE 169-2006-5C',
       'ASHRAE 169-2006-6A',
       'ASHRAE 169-2006-6B',
       'ASHRAE 169-2006-7A',
       'ASHRAE 169-2006-7B',
       'ASHRAE 169-2006-8A',
       'ASHRAE 169-2006-8B',
       'ASHRAE 169-2013-1B',
       'ASHRAE 169-2013-2B',
       'ASHRAE 169-2013-3B',
       'ASHRAE 169-2013-3C',
       'ASHRAE 169-2013-4A',
       'ASHRAE 169-2013-4B',
       'ASHRAE 169-2013-4C',
       'ASHRAE 169-2013-5A',
       'ASHRAE 169-2013-5B',
       'ASHRAE 169-2013-5C',
       'ASHRAE 169-2013-6A',
       'ASHRAE 169-2013-6B',
       'ASHRAE 169-2013-7A',
       'ASHRAE 169-2013-7B',
       'ASHRAE 169-2013-8A',
       'ASHRAE 169-2013-8B'
    is_sat_reset_required = true
    OpenStudio.logFree(OpenStudio::Info, 'openstudio.standards.AirLoopHVAC', "For #{air_loop_hvac.name}: Supply air temperature reset is required.")
    return is_sat_reset_required
  end
end

#air_terminal_single_duct_vav_reheat_apply_initial_prototype_damper_position(air_terminal_single_duct_vav_reheat, zone_oa_per_area) ⇒ Bool

Set the initial minimum damper position based on OA rate of the space and the template. Zones with low OA per area get lower initial guesses. Final position will be adjusted upward as necessary by Standards.AirLoopHVAC.apply_minimum_vav_damper_positions

Parameters:

  • zone_oa_per_area (Double)

    the zone outdoor air per area, m^3/s

Returns:

  • (Bool)

    returns true if successful, false if not



9
10
11
12
13
14
15
16
17
18
19
20
21
# File 'lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.AirTerminalSingleDuctVAVReheat.rb', line 9

def air_terminal_single_duct_vav_reheat_apply_initial_prototype_damper_position(air_terminal_single_duct_vav_reheat, zone_oa_per_area)
  min_damper_position = case air_terminal_single_duct_vav_reheat_reheat_type(air_terminal_single_duct_vav_reheat)
                        when 'HotWater'
                          0.2
                        when 'Electricity', 'NaturalGas'
                          0.3
                        end

  # Set the minimum flow fraction
  air_terminal_single_duct_vav_reheat.setConstantMinimumAirFlowFraction(min_damper_position)

  return true
end

#air_terminal_single_duct_vav_reheat_minimum_damper_position(air_terminal_single_duct_vav_reheat, has_ddc = false) ⇒ Object

Specifies the minimum damper position for VAV dampers. For terminals with hot water heat and DDC, the minimum is 20%, otherwise the minimum is 30%.

Parameters:

  • has_ddc (Bool) (defaults to: false)

    whether or not there is DDC control of the VAV terminal in question



9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
# File 'lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.AirTerminalSingleDuctVAVReheat.rb', line 9

def air_terminal_single_duct_vav_reheat_minimum_damper_position(air_terminal_single_duct_vav_reheat, has_ddc = false)
  min_damper_position = nil
  case air_terminal_single_duct_vav_reheat_reheat_type(air_terminal_single_duct_vav_reheat)
  when 'HotWater'
    min_damper_position = if has_ddc
                            0.2
                          else
                            0.3
                          end
  when 'Electricity', 'NaturalGas'
    min_damper_position = 0.3
  end

  return min_damper_position
end

#fan_constant_volume_airloop_fan_pressure_rise(fan_constant_volume) ⇒ Double

Determine the prototype fan pressure rise for a constant volume fan on an AirLoopHVAC based on the airflow of the system. to the logic from ASHRAE 90.1-2004 prototypes.

Returns:

  • (Double)

    the pressure rise (in H2O). Defaults



8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
# File 'lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.FanConstantVolume.rb', line 8

def fan_constant_volume_airloop_fan_pressure_rise(fan_constant_volume)
  # Get the max flow rate from the fan.
  maximum_flow_rate_m3_per_s = nil
  if fan_constant_volume.maximumFlowRate.is_initialized
    maximum_flow_rate_m3_per_s = fan_constant_volume.maximumFlowRate.get
  elsif fan_constant_volume.autosizedMaximumFlowRate.is_initialized
    maximum_flow_rate_m3_per_s = fan_constant_volume.autosizedMaximumFlowRate.get
  else
    OpenStudio.logFree(OpenStudio::Warn, 'openstudio.prototype.FanConstantVolume', "For #{fan_constant_volume.name} max flow rate is not available, cannot apply prototype assumptions.")
    return false
  end

  # Convert max flow rate to cfm
  maximum_flow_rate_cfm = OpenStudio.convert(maximum_flow_rate_m3_per_s, 'm^3/s', 'cfm').get

  # Determine the pressure rise
  pressure_rise_in_h2o = if maximum_flow_rate_cfm < 7437
                           2.5
                         else # Over 7,437 cfm
                           4.09
                         end

  return pressure_rise_in_h2o
end

#fan_on_off_airloop_or_unitary_fan_pressure_rise(fan_on_off) ⇒ Double

Determine the prototype fan pressure rise for an on off fan on an AirLoopHVAC or inside a unitary system based on the airflow of the system. to the logic from ASHRAE 90.1-2004 prototypes.

Returns:

  • (Double)

    the pressure rise (in H2O). Defaults



9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
# File 'lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.FanOnOff.rb', line 9

def fan_on_off_airloop_or_unitary_fan_pressure_rise(fan_on_off)
  # Get the max flow rate from the fan.
  maximum_flow_rate_m3_per_s = nil
  if fan_on_off.maximumFlowRate.is_initialized
    maximum_flow_rate_m3_per_s = fan_on_off.maximumFlowRate.get
  elsif fan_on_off.autosizedMaximumFlowRate.is_initialized
    maximum_flow_rate_m3_per_s = fan_on_off.autosizedMaximumFlowRate.get
  else
    OpenStudio.logFree(OpenStudio::Warn, 'openstudio.prototype.FanOnOff', "For #{fan_on_off.name} max flow rate is not available, cannot apply prototype assumptions.")
    return false
  end

  # Convert max flow rate to cfm
  maximum_flow_rate_cfm = OpenStudio.convert(maximum_flow_rate_m3_per_s, 'm^3/s', 'cfm').get

  # Determine the pressure rise
  pressure_rise_in_h2o = if maximum_flow_rate_cfm < 7437
                           2.5
                         else # Over 7,437 cfm
                           4.09
                         end

  return pressure_rise_in_h2o
end

#fan_variable_volume_airloop_fan_pressure_rise(fan_variable_volume) ⇒ Double

Determine the prototype fan pressure rise for a variable volume fan on an AirLoopHVAC based on the airflow of the system. to the logic from ASHRAE 90.1-2004 prototypes.

Returns:

  • (Double)

    the pressure rise (in H2O). Defaults



8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
# File 'lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.FanVariableVolume.rb', line 8

def fan_variable_volume_airloop_fan_pressure_rise(fan_variable_volume)
  # Get the max flow rate from the fan.
  maximum_flow_rate_m3_per_s = nil
  if fan_variable_volume.maximumFlowRate.is_initialized
    maximum_flow_rate_m3_per_s = fan_variable_volume.maximumFlowRate.get
  elsif fan_variable_volume.autosizedMaximumFlowRate.is_initialized
    maximum_flow_rate_m3_per_s = fan_variable_volume.autosizedMaximumFlowRate.get
  else
    OpenStudio.logFree(OpenStudio::Warn, 'openstudio.prototype.FanVariableVolume', "For #{fan_variable_volume.name} max flow rate is not available, cannot apply prototype assumptions.")
    return false
  end

  # Convert max flow rate to cfm
  maximum_flow_rate_cfm = OpenStudio.convert(maximum_flow_rate_m3_per_s, 'm^3/s', 'cfm').get

  # Determine the pressure rise
  pressure_rise_in_h2o = if maximum_flow_rate_cfm < 4648
                           4.0
                         else # Over 7,437 cfm
                           5.58
                         end

  return pressure_rise_in_h2o
end

#fan_variable_volume_part_load_fan_power_limitation_hp_limit(fan_variable_volume) ⇒ Double

TODO:

AddRef

The threhold horsepower below which part load control is not required. 10 nameplate HP threshold is equivalent to motors with input powers of 7.54 HP per TSD

Parameters:

Returns:

  • (Double)

    the limit, in horsepower. Return nil for no limit by default.



10
11
12
13
# File 'lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.FanVariableVolume.rb', line 10

def fan_variable_volume_part_load_fan_power_limitation_hp_limit(fan_variable_volume)
  hp_limit = 7.54
  return hp_limit
end

#load_standards_database(data_directories = []) ⇒ Object



13
14
15
# File 'lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.rb', line 13

def load_standards_database(data_directories = [])
  super([__dir__] + data_directories)
end

#model_create_prm_baseline_building_requires_vlt_sizing_run(model) ⇒ Object

Determine if there needs to be a sizing run after constructions are added so that EnergyPlus can calculate the VLTs of layer-by-layer glazing constructions. These VLT values are needed for the daylighting controls logic for 90.1-2010.



8
9
10
# File 'lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.Model.rb', line 8

def model_create_prm_baseline_building_requires_vlt_sizing_run(model)
  return true # Required for 90.1-2010
end

#model_economizer_type(model, climate_zone) ⇒ String

Determine the prototypical economizer type for the model.

‘NoEconomizer’ ‘FixedDryBulb’ ‘FixedEnthalpy’ ‘DifferentialDryBulb’ ‘DifferentialEnthalpy’ ‘FixedDewPointAndDryBulb’ ‘ElectronicEnthalpy’ ‘DifferentialDryBulbAndEnthalpy’

Parameters:

Returns:

  • (String)

    the economizer type. Possible values are:



17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
# File 'lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.Model.rb', line 17

def model_economizer_type(model, climate_zone)
  economizer_type = case climate_zone
                    when 'ASHRAE 169-2006-1A',
                        'ASHRAE 169-2006-2A',
                        'ASHRAE 169-2006-3A',
                        'ASHRAE 169-2006-4A',
                        'ASHRAE 169-2013-1A',
                        'ASHRAE 169-2013-2A',
                        'ASHRAE 169-2013-3A',
                        'ASHRAE 169-2013-4A'
                      'DifferentialEnthalpy'
                    else
                      'DifferentialDryBulb'
                    end
  return economizer_type
end

#model_elevator_lighting_pct_incandescent(model) ⇒ Object

Determines the percentage of the elevator cab lighting that is incandescent. The remainder is assumed to be LED. Defaults to 0% incandescent (100% LED), representing newer elevators.



8
9
10
11
# File 'lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.Model.elevators.rb', line 8

def model_elevator_lighting_pct_incandescent(model)
  pct_incandescent = 0.0 # 100% LED
  return pct_incandescent
end

#model_prm_baseline_system_number(model, climate_zone, area_type, fuel_type, area_ft2, num_stories, custom) ⇒ String

Determines which system number is used for the baseline system. 5_or_6, 7_or_8, 9_or_10

Returns:

  • (String)

    the system number: 1_or_2, 3_or_4,



16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
# File 'lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.Model.rb', line 16

def model_prm_baseline_system_number(model, climate_zone, area_type, fuel_type, area_ft2, num_stories, custom)
  sys_num = nil

  # Set the area limit
  limit_ft2 = 25_000

  # Customization for Xcel EDA.
  # No special retail category
  # for regular 90.1-2010.
  unless custom == 'Xcel Energy CO EDA'
    if area_type == 'retail'
      area_type = 'nonresidential'
    end
  end

  case area_type
  when 'residential'
    sys_num = '1_or_2'
  when 'nonresidential'
    # nonresidential and 3 floors or less and <25,000 ft2
    if num_stories <= 3 && area_ft2 < limit_ft2
      sys_num = '3_or_4'
    # nonresidential and 4 or 5 floors or 5 floors or less and 25,000 ft2 to 150,000 ft2
    elsif ((num_stories == 4 || num_stories == 5) && area_ft2 < limit_ft2) || (num_stories <= 5 && (area_ft2 >= limit_ft2 && area_ft2 <= 150_000))
      sys_num = '5_or_6'
    # nonresidential and more than 5 floors or >150,000 ft2
    elsif num_stories >= 5 || area_ft2 > 150_000
      sys_num = '7_or_8'
    end
  when 'heatedonly'
    sys_num = '9_or_10'
  when 'retail'
    # Should only be hit by Xcel EDA
    sys_num = '3_or_4'
  end

  return sys_num
end

#space_daylighted_area_window_width(space) ⇒ String

Determines the method used to extend the daylighted area horizontally next to a window. If the method is ‘fixed’, 2 ft is added to the width of each window. If the method is ‘proportional’, a distance equal to half of the head height of the window is added. If the method is ‘none’, no additional width is added.

Returns:

  • (String)

    returns ‘fixed’ or ‘proportional’



11
12
13
14
# File 'lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.Space.rb', line 11

def space_daylighted_area_window_width(space)
  method = 'fixed'
  return method
end

#space_daylighting_control_required?(space, areas) ⇒ Array<Bool>

Determine if the space requires daylighting controls for toplighting, primary sidelighting, and secondary sidelighting. Defaults to false for all types.

Parameters:

Returns:

  • (Array<Bool>)

    req_top_ctrl, req_pri_ctrl, req_sec_ctrl



23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
# File 'lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.Space.rb', line 23

def space_daylighting_control_required?(space, areas)
  req_top_ctrl = true
  req_pri_ctrl = true
  req_sec_ctrl = false

  OpenStudio.logFree(OpenStudio::Debug, 'openstudio.model.Space', "primary_sidelighted_area = #{areas['primary_sidelighted_area']}")

  # Sidelighting
  # Check if the primary sidelit area < 250 ft2
  if areas['primary_sidelighted_area'] == 0.0
    OpenStudio.logFree(OpenStudio::Debug, 'openstudio.model.Space', "For #{space.name}, primary sidelighting control not required because primary sidelighted area = 0ft2 per 9.4.1.4.")
    req_pri_ctrl = false
  elsif areas['primary_sidelighted_area'] < OpenStudio.convert(250, 'ft^2', 'm^2').get
    OpenStudio.logFree(OpenStudio::Info, 'openstudio.model.Space', "For #{space.name}, primary sidelighting control not required because primary sidelighted area less than 250ft2 per 9.4.1.4.")
    req_pri_ctrl = false
  else
    # Check effective sidelighted aperture
    sidelighted_effective_aperture = space_sidelighting_effective_aperture(space, areas['primary_sidelighted_area'])
    OpenStudio.logFree(OpenStudio::Debug, 'openstudio.model.Space', "sidelighted_effective_aperture_pri = #{sidelighted_effective_aperture}")
    if sidelighted_effective_aperture < 0.1 and @instvarbuilding_type.nil?
      OpenStudio.logFree(OpenStudio::Info, 'openstudio.model.Space', "For #{space.name}, primary sidelighting control not required because sidelighted effective aperture less than 0.1 per 9.4.1.4 Exception b.")
      req_pri_ctrl = false
    end
  end

  OpenStudio.logFree(OpenStudio::Debug, 'openstudio.model.Space', "toplighted_area = #{areas['toplighted_area']}")

  # Toplighting
  # Check if the toplit area < 900 ft2
  if areas['toplighted_area'] == 0.0
    OpenStudio.logFree(OpenStudio::Debug, 'openstudio.model.Space', "For #{space.name}, toplighting control not required because toplighted area = 0ft2 per 9.4.1.5.")
    req_top_ctrl = false
  elsif areas['toplighted_area'] < OpenStudio.convert(900, 'ft^2', 'm^2').get
    OpenStudio.logFree(OpenStudio::Info, 'openstudio.model.Space', "For #{space.name}, toplighting control not required because toplighted area less than 900ft2 per 9.4.1.5.")
    req_top_ctrl = false
  else
    # Check effective sidelighted aperture
    sidelighted_effective_aperture = space_skylight_effective_aperture(space, areas['toplighted_area'])
    OpenStudio.logFree(OpenStudio::Debug, 'openstudio.model.Space', "sidelighted_effective_aperture_top = #{sidelighted_effective_aperture}")
    if sidelighted_effective_aperture < 0.006
      OpenStudio.logFree(OpenStudio::Info, 'openstudio.model.Space', "For #{space.name}, toplighting control not required because skylight effective aperture less than 0.006 per 9.4.1.5 Exception b.")
      req_top_ctrl = false
    end
  end

  # Exceptions
  if space.spaceType.is_initialized
    case space.spaceType.get.standardsSpaceType.to_s
    # Retail spaces exception (c) to Section 9.4.1.4
    # req_sec_ctrl set to true to create a second reference point
    when 'Core_Retail'
      req_pri_ctrl = false
      req_sec_ctrl = true
    when 'Entry', 'Front_Retail', 'Point_of_Sale'
      req_pri_ctrl = false
      req_sec_ctrl = false
    # Strip mall
    when 'Strip mall - type 1', 'Strip mall - type 2', 'Strip mall - type 3', 'Strip mall - type 0A', 'Strip mall - type 0B'
      req_pri_ctrl = false
      req_sec_ctrl = false
    # Residential apartments
    when 'Apartment', 'Apartment_topfloor_NS', 'Apartment_topfloor_WE'
      req_top_ctrl = false
      req_pri_ctrl = false
      req_sec_ctrl = false
    end
  end

  return [req_top_ctrl, req_pri_ctrl, req_sec_ctrl]
end

#space_daylighting_fractions_and_windows(space, areas, sorted_windows, sorted_skylights, req_top_ctrl, req_pri_ctrl, req_sec_ctrl) ⇒ Object

Determine the fraction controlled by each sensor and which window each sensor should go near.

Parameters:

  • space (OpenStudio::Model::Space)

    the space with the daylighting

  • sorted_windows (Hash)

    a hash of windows, sorted by priority

  • sorted_skylights (Hash)

    a hash of skylights, sorted by priority

  • req_top_ctrl (Bool)

    if toplighting controls are required

  • req_pri_ctrl (Bool)

    if primary sidelighting controls are required

  • req_sec_ctrl (Bool)

    if secondary sidelighting controls are required



103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
# File 'lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.Space.rb', line 103

def space_daylighting_fractions_and_windows(space,
                                            areas,
                                            sorted_windows,
                                            sorted_skylights,
                                            req_top_ctrl,
                                            req_pri_ctrl,
                                            req_sec_ctrl)
  sensor_1_frac = 0.0
  sensor_2_frac = 0.0
  sensor_1_window = nil
  sensor_2_window = nil

  # Get the area of the space
  space_area_m2 = space.floorArea

  if req_top_ctrl && req_pri_ctrl
    # Sensor 1 controls toplighted area
    sensor_1_frac = areas['toplighted_area'] / space_area_m2
    sensor_1_window = sorted_skylights[0]
    # Sensor 2 controls primary area
    sensor_2_frac = areas['primary_sidelighted_area'] / space_area_m2
    sensor_2_window = sorted_windows[0]
  elsif req_top_ctrl && !req_pri_ctrl
    # Sensor 1 controls toplighted area
    sensor_1_frac = areas['toplighted_area'] / space_area_m2
    sensor_1_window = sorted_skylights[0]
  elsif req_top_ctrl && !req_pri_ctrl && req_sec_ctrl
    # Sensor 1 controls toplighted area
    sensor_1_frac = areas['toplighted_area'] / space_area_m2
    sensor_1_window = sorted_skylights[0]
    # Sensor 2 controls secondary area
    sensor_2_frac = (areas['secondary_sidelighted_area'] / space_area_m2)
    # sorted_skylights[0] assigned to sensor_2_window so a second reference point is added for top daylighting
    sensor_2_window = sorted_skylights[0]
  elsif !req_top_ctrl && req_pri_ctrl
    if sorted_windows.size == 1
      # Sensor 1 controls the whole primary area
      sensor_1_frac = areas['primary_sidelighted_area'] / space_area_m2
      sensor_1_window = sorted_windows[0]
    else
      # Sensor 1 controls half the primary area
      sensor_1_frac = (areas['primary_sidelighted_area'] / space_area_m2) / 2
      sensor_1_window = sorted_windows[0]
      # Sensor 2 controls the other half of primary area
      sensor_2_frac = (areas['primary_sidelighted_area'] / space_area_m2) / 2
      sensor_2_window = sorted_windows[1]
    end
  end

  return [sensor_1_frac, sensor_2_frac, sensor_1_window, sensor_2_window]
end

#space_infiltration_rate_75_pa(space) ⇒ Double

Determine the base infiltration rate at 75 PA.

defaults to no infiltration.

Returns:

  • (Double)

    the baseline infiltration rate, in cfm/ft^2



159
160
161
162
# File 'lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.Space.rb', line 159

def space_infiltration_rate_75_pa(space)
  basic_infil_rate_cfm_per_ft2 = 1.0
  return basic_infil_rate_cfm_per_ft2
end

#thermal_zone_demand_control_ventilation_limits(thermal_zone) ⇒ Array<Double>

Determine the area and occupancy level limits for demand control ventilation.

and the minimum occupancy density in m^2/person. Returns nil if there is no requirement.

Parameters:

Returns:

  • (Array<Double>)

    the minimum area, in m^2



11
12
13
14
15
16
17
18
19
20
21
22
# File 'lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.ThermalZone.rb', line 11

def thermal_zone_demand_control_ventilation_limits(thermal_zone)
  min_area_ft2 = 500
  min_occ_per_1000_ft2 = 40

  # Convert to SI
  min_area_m2 = OpenStudio.convert(min_area_ft2, 'ft^2', 'm^2').get
  min_occ_per_ft2 = min_occ_per_1000_ft2 / 1000.0
  min_ft2_per_occ = 1.0 / min_occ_per_ft2
  min_m2_per_occ = OpenStudio.convert(min_ft2_per_occ, 'ft^2', 'm^2').get

  return [min_area_m2, min_m2_per_occ]
end