Module: CoilDX

Included in:
Standard
Defined in:
lib/openstudio-standards/standards/Standards.CoilDX.rb

Overview

A variety of DX coil methods that are the same regardless of coil type. These methods are available to: CoilCoolingDXSingleSpeed, CoilCoolingDXTwoSpeed, CoilCoolingDXMultiSpeed

CoilDX collapse

Instance Method Details

#coil_dx_find_search_criteria(coil_dx) ⇒ hash

Finds the search criteria

Returns:

  • (hash)

    has for search criteria to be used for find object



135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
# File 'lib/openstudio-standards/standards/Standards.CoilDX.rb', line 135

def coil_dx_find_search_criteria(coil_dx)
  search_criteria = {}
  search_criteria['template'] = template

  search_criteria['cooling_type'] = case coil_dx.iddObjectType.valueName.to_s
                                    when 'OS_Coil_Cooling_DX_SingleSpeed',
                                         'OS_Coil_Cooling_DX_TwoSpeed',
                                         'OS_Coil_Cooling_DX_MultiSpeed'
                                      coil_dx.condenserType
                                    else
                                      'AirCooled'
                                    end

  # Get the coil_dx_subcategory(coil_dx)
  search_criteria['subcategory'] = coil_dx_subcategory(coil_dx)

  # Add the heating type to the search criteria
  htg_type = coil_dx_heating_type(coil_dx)
  unless htg_type.nil?
    search_criteria['heating_type'] = htg_type
  end

  # The heating side of unitary heat pumps don't have a heating type
  # as part of the search
  if coil_dx.to_CoilHeatingDXSingleSpeed.is_initialized
    if coil_dx_heat_pump?(coil_dx)
      if coil_dx.airLoopHVAC.empty?
        if coil_dx.containingHVACComponent.is_initialized
          containing_comp = coil_dx.containingHVACComponent.get
          if containing_comp.to_AirLoopHVACUnitaryHeatPumpAirToAir.is_initialized
            search_criteria['heating_type'] = nil
          end # TODO: Add other unitary systems
        end
      end
    end
  end

  return search_criteria
end

#coil_dx_heat_pump?(coil_dx) ⇒ Bool

Determine if it is a heat pump

Returns:

  • (Bool)

    true if it is a heat pump, false if not



47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
# File 'lib/openstudio-standards/standards/Standards.CoilDX.rb', line 47

def coil_dx_heat_pump?(coil_dx)
  heat_pump = false

  if coil_dx.airLoopHVAC.empty?
    if coil_dx.containingHVACComponent.is_initialized
      containing_comp = coil_dx.containingHVACComponent.get
      if containing_comp.to_AirLoopHVACUnitaryHeatPumpAirToAir.is_initialized
        heat_pump = true
      end # TODO: Add other unitary systems
    elsif coil_dx.containingZoneHVACComponent.is_initialized
      containing_comp = coil_dx.containingZoneHVACComponent.get
      # PTHP
      if containing_comp.to_ZoneHVACPackagedTerminalHeatPump.is_initialized
        heat_pump = true
      end # TODO: Add other zone hvac systems
    end
  end

  return heat_pump
end

#coil_dx_heating_type(coil_dx) ⇒ String

Determine the heating type. Possible choices are: Electric Resistance or None, All Other

Returns:

  • (String)

    the heating type



71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
# File 'lib/openstudio-standards/standards/Standards.CoilDX.rb', line 71

def coil_dx_heating_type(coil_dx)
  htg_type = nil

  # If Unitary or Zone HVAC
  if coil_dx.airLoopHVAC.empty?
    if coil_dx.containingHVACComponent.is_initialized
      containing_comp = coil_dx.containingHVACComponent.get
      if containing_comp.to_AirLoopHVACUnitaryHeatPumpAirToAir.is_initialized
        htg_type = 'Electric Resistance or None'
      elsif containing_comp.to_AirLoopHVACUnitarySystem.is_initialized
        if containing_comp.name.to_s.include? 'Minisplit'
          htg_type = 'All Other'
        end
      end # TODO: Add other unitary systems
    elsif coil_dx.containingZoneHVACComponent.is_initialized
      containing_comp = coil_dx.containingZoneHVACComponent.get
      # PTAC
      if containing_comp.to_ZoneHVACPackagedTerminalAirConditioner.is_initialized
        htg_coil = containing_comp.to_ZoneHVACPackagedTerminalAirConditioner.get.heatingCoil
        if htg_coil.to_CoilHeatingElectric.is_initialized
          htg_type = 'Electric Resistance or None'
        elsif htg_coil.to_CoilHeatingWater.is_initialized || htg_coil.to_CoilHeatingGas.is_initialized
          htg_type = 'All Other'
        end
      # PTHP
      elsif containing_comp.to_ZoneHVACPackagedTerminalHeatPump.is_initialized
        htg_type = 'Electric Resistance or None'
      end # TODO: Add other zone hvac systems

    end
  end

  # If on an AirLoop
  if coil_dx.airLoopHVAC.is_initialized
    air_loop = coil_dx.airLoopHVAC.get
    htg_type = if !air_loop.supplyComponents('OS:Coil:Heating:Gas'.to_IddObjectType).empty?
                 'All Other'
               elsif !air_loop.supplyComponents('OS:Coil:Heating:Water'.to_IddObjectType).empty?
                 'All Other'
               elsif !air_loop.supplyComponents('OS:Coil:Heating:DX:SingleSpeed'.to_IddObjectType).empty?
                 'All Other'
               elsif !air_loop.supplyComponents('OS:Coil:Heating:DX:MultiSpeed'.to_IddObjectType).empty?
                 'All Other'
               elsif !air_loop.supplyComponents('OS:Coil:Heating:DX:VariableSpeed'.to_IddObjectType).empty?
                 'All Other'
               elsif !air_loop.supplyComponents('OS:Coil:Heating:Gas:MultiStage'.to_IddObjectType).empty?
                 'All Other'
               elsif !air_loop.supplyComponents('OS:Coil:Heating:Desuperheater'.to_IddObjectType).empty?
                 'All Other'
               elsif !air_loop.supplyComponents('OS:Coil:Heating:WaterToAirHeatPump:EquationFit'.to_IddObjectType).empty?
                 'All Other'
               elsif !air_loop.supplyComponents('OS:Coil:Heating:Electric'.to_IddObjectType).empty?
                 'Electric Resistance or None'
               else
                 'Electric Resistance or None'
               end
  end

  return htg_type
end

#coil_dx_subcategory(coil_dx) ⇒ String

TODO:

Add add split system vs single package to model object

Finds the subcategory. Possible choices are: Single Package, Split System, PTAC, or PTHP

Returns:

  • (String)

    the coil_dx_subcategory(coil_dx)



13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
# File 'lib/openstudio-standards/standards/Standards.CoilDX.rb', line 13

def coil_dx_subcategory(coil_dx)
  sub_category = 'Single Package'

  # Fallback to the name, mainly for library export
  if coil_dx.name.get.to_s.include?('Single Package')
    sub_category = 'Single Package'
  elsif coil_dx.name.get.to_s.include?('Split System')
    sub_category = 'Split System'
  elsif coil_dx.name.get.to_s.include?('Central Air Source HP')
    sub_category = 'Split System'
  elsif coil_dx.name.get.to_s.include?('Minisplit HP')
    sub_category = 'Minisplit System'
  elsif coil_dx.name.get.to_s.include?('CRAC')
    sub_category = 'CRAC'
  end

  if coil_dx.airLoopHVAC.empty?
    if coil_dx.containingZoneHVACComponent.is_initialized
      containing_comp = coil_dx.containingZoneHVACComponent.get
      # PTAC
      if containing_comp.to_ZoneHVACPackagedTerminalAirConditioner.is_initialized
        sub_category = 'PTAC'
      # PTHP
      elsif containing_comp.to_ZoneHVACPackagedTerminalHeatPump.is_initialized
        sub_category = 'PTHP'
      end # TODO: Add other zone hvac systems
    end
  end

  return sub_category
end